Adebayo Adelabu, the minister for Power has shared a statement on what caused the national grid collapse that has resulted in the general power outage experienced all over the country.
Adelabu said there was a fire at the Kainji/Jebba line, but the outbreak has been taken care of.
He wrote, “At 00:35Hrs this morning, a fire outbreak with an explosion sound was observed on Kainji/Jebba 330kV line 2 (Cct K2J) blue phase CVT & Blue phase line Isolator of Kainji/Jebba 330kV line1 was observed burning.
“This led to sharp drops in frequency from 50.29Hz to 49.67 Hz at 0:35:06Hrs with Jebba generation loss of 356.63MW. Kainji started dropping load from 451.45 MW at 00:35:07Hrs to zero.
“At 00:41Hrs frequency dropped further from 49.37 Hz to 48.41 Hz resulting in system collapse of the grid. We are on top of the situation and speedy restoration is in progress.
“The fire has been fully arrested and over half of the connections are now up and the rest will be fully restored in no time.
He however expressed sincere appreciation to those who responded and the team of Engineers for their prompt response to the situation and the work done so far.
He said, “Let’s get the restoration work completed as soon as possible. The delay in the update was deliberate, so as not to cause panic and to also be able to update on the progress of remedial actions taken so far. This is to ensure economic and security saboteurs don’t take advantage of every situation reported.”